Common fault effects on a natural refrigerant, variable-speed heat pump - imarina:9241734

URV's Author/s:Bellanco Bellanco, Ivan / Vallès Rasquera, Joan Manel
Author, as appears in the article.:Bellanco, I; Belio, F.; Valles, M.; Gerber, R.; Salom, J.;
Author's mail:ivan.bellanco@estudiants.urv.cat
manel.valles@urv.cat
Author identifier:0000-0002-0748-1287
Journal publication year:2022
Publication Type:Journal Publications
APA:Bellanco, I; Belio, F.; Valles, M.; Gerber, R.; Salom, J.; (2022). Common fault effects on a natural refrigerant, variable-speed heat pump. International Journal Of Refrigeration-Revue Internationale Du Froid, 133(), 259-266. DOI: 10.1016/j.ijrefrig.2021.10.017
Papper original source:International Journal Of Refrigeration-Revue Internationale Du Froid. 133 259-266
Abstract:The European heat pump market is growing every year as European legislation moves towards the use of natural refrigerants that have less global warming potential than conventional refrigerants. Even though heat pumps are very efficient, the appearance of hard-to-detect faults increases energy consumption. The present study emulated some of the most common faults on a variable-speed heat pump charged with propane. The faults tested were evaporator fouling, compressor valve leakage, liquid line restriction and refrigerant overcharge. The effect of these faults on performance and several heat pump features are described. Evaporator fouling was the fault with least COP degradation and compressor valve leakage with the most (7% and 56% COP reduction, respectively). The results are compared with the results from a comparable study. The heat pump covered the demand generated by nearly all the faults at the expense of increasing the power consumption. The features of each fault are summarized in a chart, which could be used as table for diagnosing faults.
Article's DOI:10.1016/j.ijrefrig.2021.10.017
Link to the original source:https://www.sciencedirect.com/science/article/pii/S0140700721004114#:~:text=The%20present%20study%20emulated%20some,heat%20pump%20features%20are%20described.
Papper version:info:eu-repo/semantics/publishedVersion
licence for use:https://creativecommons.org/licenses/by/3.0/es/
Department:Enginyeria Mecànica
Licence document URL:https://repositori.urv.cat/ca/proteccio-de-dades/
Thematic Areas:Thermodynamics
Química
Mechanical engineering
Materiais
Interdisciplinar
Engineering, mechanical
Engenharias iv
Engenharias iii
Engenharias ii
Ciência de alimentos
Building and construction
Astronomia / física
Keywords:Variable speed
Variable refrigerant flow system
Valve leakage
System
Refrigerants
Refrigerant flow
Pumps
Performance
Natural refrigerants
Mode
Heat pumps
Heat pump systems
Global warming
Flow systems
Fault effect
Fault detection and diagnosis
Fault detection
Failure analysis
Evaporators
Energy utilization
Diagnostics
Common faults