Autor segons l'article: Chen, Yongyang; Huang, Meng; Pan, Shangzhi; El Aroudi, Abdelali; Zha, Xiaoming
Departament: Enginyeria Electrònica, Elèctrica i Automàtica
Autor/s de la URV: El Aroudi Chaoui, Abdelali
Paraules clau: Transient analysis Switches Sub-module voltage stress Stress Short-circuit Multiterminal hvdc grids Multi-terminal dc transmission system Modular multilevel converter Location Integrated circuit modeling Fault current analysis Equivalent circuits Discrete-time model Converter Circuit faults Capacitors
Resum: IEEE Transient voltage and current stresses are essential for the design and protection of multi-terminal DC (MTDC) transmission systems, especially under the short-term dynamics after severe grid faults. In this paper, we propose a discrete-time model for the modular multilevel converter based MTDC (MMC-MTDC) system considering the DC-side disturbances in the system. Based on the piecewise linear modeling, the state variables such as the transient voltage on the sub-module (SM), arm current, etc., can be calculated analytically for the critical short term (within 10 ms) after the severe DC fault while the system protection is yet to be activated. Parameter sensitivity analysis is also performed to give a better system design guideline. The estimation results are validated by detailed electromagnetic (EMT) circuit simulations and the scaled-down experimental laboratory prototype.
Àrees temàtiques: Materiais Matemática / probabilidade e estatística Interdisciplinar Engineering, electrical & electronic Engenharias iv Engenharias iii Engenharias ii Energy engineering and power technology Electrical and electronic engineering Ciências ambientais Ciências agrárias i Ciência da computação
Accès a la llicència d'ús: https://creativecommons.org/licenses/by/3.0/es/
Adreça de correu electrònic de l'autor: abdelali.elaroudi@urv.cat
Identificador de l'autor: 0000-0001-9103-7762
Data d'alta del registre: 2024-10-12
Versió de l'article dipositat: info:eu-repo/semantics/acceptedVersion
Enllaç font original: https://ieeexplore.ieee.org/document/8964448
URL Document de llicència: https://repositori.urv.cat/ca/proteccio-de-dades/
Referència a l'article segons font original: Ieee Transactions On Power Delivery. 35 (6): 2821-2830
Referència de l'ítem segons les normes APA: Chen, Yongyang; Huang, Meng; Pan, Shangzhi; El Aroudi, Abdelali; Zha, Xiaoming (2020). Transient Voltage and Current Stresses Estimation of MMC-MTDC System via Discrete-time Analysis. Ieee Transactions On Power Delivery, 35(6), 2821-2830. DOI: 10.1109/TPWRD.2020.2968389
DOI de l'article: 10.1109/TPWRD.2020.2968389
Entitat: Universitat Rovira i Virgili
Any de publicació de la revista: 2020
Tipus de publicació: Journal Publications