Autor segons l'article: Ramos, ER; Leyva, R; Liu, QX; Farivar, GG; Pou, J
Departament: Enginyeria Electrònica, Elèctrica i Automàtica
Autor/s de la URV: Leyva Grasa, Ramon
Paraules clau: Voltage measurement Static compensator (statcom) Reliability Oscillators Monitoring Frequency conversion Estimation Equivalent series resistance (esr) Diagnostics Dc-link capacitor Condition monitoring Cascaded h-bridge (chb) Capacitors Capacitance Automatic voltage control static compensator (statcom) reliability estimation equivalent series resistance (esr) diagnostics dc-link capacitor condition monitoring
Resum: The cascaded H-bridge low-capacitance static compensator (LC-StatCom) deliberately reduces the capacitor size while allowing large oscillations in capacitor voltages. When a capacitor deteriorates, its capacitance decreases or/and its equivalent series resistance (ESR) increases, compromising StatCom performance and safety. For this reason, the condition monitoring of the capacitors is important to schedule maintenance before failure. This letter introduces a cost-effective and nonintrusive method to monitor the condition of capacitors online. The proposed method offers real-time monitoring without requiring additional hardware or signal injection. The method uses averaged low-frequency signals instead of instantaneous high-frequency signals that can be corrupted by undesired high-frequency noise. Specifically, the method takes advantage of the inherent twice-fundamental-frequency oscillations on the capacitor voltage and current to identify the ESR and capacitance values. The method takes into account the influence of antialiasing filters required for sampling process. The letter shows experimental results that validate the fast and accurate performance of the proposed capacitor condition monitoring.
Àrees temàtiques: Interdisciplinar Engineering, electrical & electronic Engenharias iv Engenharias iii Electrical and electronic engineering Ciências agrárias i Ciência da computação
Adreça de correu electrònic de l'autor: ramon.leyva@urv.cat
Identificador de l'autor: 0000-0001-6431-3688
Data d'alta del registre: 2024-08-03
Versió de l'article dipositat: info:eu-repo/semantics/acceptedVersion
URL Document de llicència: https://repositori.urv.cat/ca/proteccio-de-dades/
Referència a l'article segons font original: Ieee Transactions On Power Electronics. 38 (9): 10559-10562
Referència de l'ítem segons les normes APA: Ramos, ER; Leyva, R; Liu, QX; Farivar, GG; Pou, J (2023). Capacitor Condition Monitoring Method for Low-Capacitance StatComs: An Online Approach Using the Inherent Second-Harmonic Oscillations. Ieee Transactions On Power Electronics, 38(9), 10559-10562. DOI: 10.1109/TPEL.2023.3286447
Entitat: Universitat Rovira i Virgili
Any de publicació de la revista: 2023
Tipus de publicació: Journal Publications