Feasibility study and performance evaluation of low capacity water-LiBr absorption cooling systems functioning in different Algerian climate zones

  • Datos identificativos

    Identificador: imarina:5131367
    Autores:
    Ketfi, OmarMerzouk, MustaphaMerzouk, Nachida KasbadjiBourouis, Mahmoud
    Resumen:
    A performance analysis was carried out on water¿LiBr absorption chillers performing in the five different climate zones in Algeria. A 17.6 kW single-effect and a 16 kW double-effect commercial absorption chillers were simulated. In climate zones E1 and E2, the single-effect and double-effect chillers supplied 37% and 91%, respectively, of their nominal capacity to produce chilled water at 7 °C. In the hot climate zones E3, E4 and E5, it was not feasible for either of the chillers to produce chilled water at 7 °C. By increasing the chilled water temperature to 12 °C both absorption chillers were able to operate in climate zones E3 and E4. The single-effect chiller reached 45% of its nominal capacity in zone E3 and 33% in zone E4. The double-effect chiller delivered 80% of its nominal capacity in both climate zones. Neither of the chillers was able to operate under the thermal conditions of climate zone E5.
  • Otros:

    Autor según el artículo: Ketfi, Omar; Merzouk, Mustapha; Merzouk, Nachida Kasbadji; Bourouis, Mahmoud
    Departamento: Enginyeria Mecànica
    Autor/es de la URV: Bourouis Chebata, Mahmoud
    Palabras clave: Water–libr Thermal cooling Climate zones in algeria Absorption chillers
    Resumen: A performance analysis was carried out on water¿LiBr absorption chillers performing in the five different climate zones in Algeria. A 17.6 kW single-effect and a 16 kW double-effect commercial absorption chillers were simulated. In climate zones E1 and E2, the single-effect and double-effect chillers supplied 37% and 91%, respectively, of their nominal capacity to produce chilled water at 7 °C. In the hot climate zones E3, E4 and E5, it was not feasible for either of the chillers to produce chilled water at 7 °C. By increasing the chilled water temperature to 12 °C both absorption chillers were able to operate in climate zones E3 and E4. The single-effect chiller reached 45% of its nominal capacity in zone E3 and 33% in zone E4. The double-effect chiller delivered 80% of its nominal capacity in both climate zones. Neither of the chillers was able to operate under the thermal conditions of climate zone E5.
    Áreas temáticas: Thermodynamics Química Mechanical engineering Materiais Interdisciplinar Engineering, mechanical Engenharias iv Engenharias iii Engenharias ii Ciência de alimentos Building and construction Astronomia / física
    Acceso a la licencia de uso: https://creativecommons.org/licenses/by/3.0/es/
    Direcció de correo del autor: mahmoud.bourouis@urv.cat
    Identificador del autor: 0000-0003-2476-5967
    Fecha de alta del registro: 2024-09-07
    Versión del articulo depositado: info:eu-repo/semantics/acceptedVersion
    Enlace a la fuente original: https://www.sciencedirect.com/science/article/abs/pii/S0140700717302815?via%3Dihub
    URL Documento de licencia: https://repositori.urv.cat/ca/proteccio-de-dades/
    Referencia al articulo segun fuente origial: International Journal Of Refrigeration-Revue Internationale Du Froid. 82 36-50
    Referencia de l'ítem segons les normes APA: Ketfi, Omar; Merzouk, Mustapha; Merzouk, Nachida Kasbadji; Bourouis, Mahmoud (2017). Feasibility study and performance evaluation of low capacity water-LiBr absorption cooling systems functioning in different Algerian climate zones. International Journal Of Refrigeration-Revue Internationale Du Froid, 82(), 36-50. DOI: 10.1016/j.ijrefrig.2017.07.002
    DOI del artículo: 10.1016/j.ijrefrig.2017.07.002
    Entidad: Universitat Rovira i Virgili
    Año de publicación de la revista: 2017
    Tipo de publicación: Journal Publications
  • Palabras clave:

    Building and Construction,Engineering, Mechanical,Mechanical Engineering,Thermodynamics
    Water–libr
    Thermal cooling
    Climate zones in algeria
    Absorption chillers
    Thermodynamics
    Química
    Mechanical engineering
    Materiais
    Interdisciplinar
    Engineering, mechanical
    Engenharias iv
    Engenharias iii
    Engenharias ii
    Ciência de alimentos
    Building and construction
    Astronomia / física
  • Documentos:

  • Cerca a google

    Search to google scholar