Autor según el artículo: Ketfi, Omar; Merzouk, Mustapha; Merzouk, Nachida Kasbadji; Bourouis, Mahmoud
Departamento: Enginyeria Mecànica
Autor/es de la URV: Bourouis Chebata, Mahmoud
Palabras clave: Water–libr Thermal cooling Climate zones in algeria Absorption chillers
Resumen: A performance analysis was carried out on water¿LiBr absorption chillers performing in the five different climate zones in Algeria. A 17.6 kW single-effect and a 16 kW double-effect commercial absorption chillers were simulated. In climate zones E1 and E2, the single-effect and double-effect chillers supplied 37% and 91%, respectively, of their nominal capacity to produce chilled water at 7 °C. In the hot climate zones E3, E4 and E5, it was not feasible for either of the chillers to produce chilled water at 7 °C. By increasing the chilled water temperature to 12 °C both absorption chillers were able to operate in climate zones E3 and E4. The single-effect chiller reached 45% of its nominal capacity in zone E3 and 33% in zone E4. The double-effect chiller delivered 80% of its nominal capacity in both climate zones. Neither of the chillers was able to operate under the thermal conditions of climate zone E5.
Áreas temáticas: Thermodynamics Química Mechanical engineering Materiais Interdisciplinar Engineering, mechanical Engenharias iv Engenharias iii Engenharias ii Ciência de alimentos Building and construction Astronomia / física
Acceso a la licencia de uso: https://creativecommons.org/licenses/by/3.0/es/
Direcció de correo del autor: mahmoud.bourouis@urv.cat
Identificador del autor: 0000-0003-2476-5967
Fecha de alta del registro: 2024-09-07
Versión del articulo depositado: info:eu-repo/semantics/acceptedVersion
Enlace a la fuente original: https://www.sciencedirect.com/science/article/abs/pii/S0140700717302815?via%3Dihub
URL Documento de licencia: https://repositori.urv.cat/ca/proteccio-de-dades/
Referencia al articulo segun fuente origial: International Journal Of Refrigeration-Revue Internationale Du Froid. 82 36-50
Referencia de l'ítem segons les normes APA: Ketfi, Omar; Merzouk, Mustapha; Merzouk, Nachida Kasbadji; Bourouis, Mahmoud (2017). Feasibility study and performance evaluation of low capacity water-LiBr absorption cooling systems functioning in different Algerian climate zones. International Journal Of Refrigeration-Revue Internationale Du Froid, 82(), 36-50. DOI: 10.1016/j.ijrefrig.2017.07.002
DOI del artículo: 10.1016/j.ijrefrig.2017.07.002
Entidad: Universitat Rovira i Virgili
Año de publicación de la revista: 2017
Tipo de publicación: Journal Publications